Why is FM-200 Fire Suppression System Not Working

Why is FM-200 Fire Suppression System Not Working

Views : 1593
Update time : 2022-11-08 17:37:18
FM-200 is a colorless, odorless halocarbon. It can extinguish the fire by effectively preventing the chemical reaction that allows a fire to burn. FM-200 fire suppression systems are used to suppress fires in specific hazards or equipment located where an electrically non-conductive agent is required, and where agent cleanup creates a problem.

When people use the FM-200 fire suppression systems, sometimes they don't work. If it happens, it might be for the following reasons:
1.The gas suppression system control panel is in manual control mode.
There are 3 ways for the FM-200 to be activated: the automatic start-up mode, the electric manual start-up mode, and the mechanical emergency manual start-up mode. In the electrical manual start-up mode, the fire detection system can only detect and alarm the protected zone, and can’t turn on the fire extinguishing devices by itself. It needs to manually press the start-up button on the fire alarm control panel or the emergency start and stop button outside the protected zone’s door, so that the fire alarm control system can receive the starting signal and turn on the fire extinguishing devices according to the predetermined procedure.

2.The solenoid valve is not installed correctly or the safety pin is not pulled out.
The electromagnetic drive device is installed on the container valve. When the fire is being extinguished, the electromagnet will break down the safety diaphragm on the container valve to release the fire extinguishing agent. If it is not installed correctly, the fire extinguishing agent will not be released, causing the failure of putting out a fire.

3.The starting power is not enough.
If a fire occurs, and the power distributed by the fire extinguishing device is not enough, the solenoid valve might not be driven, the electromagnet might not act and the safety diaphragm on the container valve might not be broken down, making the FM-200 fire suppression system fail to start up, or some parts of it fail to start up.

4.FM-200 fire suppression system is not regularly tested according to regulations.
If the FM-200 fire suppression system is not tested regularly according to the regulations, it will lead to the result where there might be a leakage of the fire extinguishing agent, making the dosage of the agent fail to reach a certain amount, and causing the failure of putting out a fire or the fire extinguishing agent fail to be sprayed.
5.Other reasons.
For example, the selector valve has been in disrepair for a long time, resulting in insensitive action and failure to effectively spray the fire extinguishing agent. Or the equipment pressure is abnormal, resulting in the failure of the fire extinguishing a
Related News
Read More >>
What is Fire Hose? What is Fire Hose?
Oct .13.2023
A fire hose is a highly pressurized hose that is used to bring water to the fire. It may also transport flame retardants. Fire hoses can be attached to either a fire engine or a fire hydrant, and the pressure is between 800 and 2000 kPa. For reasons of fire safety, it's quite important to have a fire hose inspection as well as all fire protection equipment tested.  If, during a fire emergency, the fire hose fails it could have disastrous results.
Addressable Explosion-proof Fire Alarm System Introduction Addressable Explosion-proof Fire Alarm System Introduction
Aug .08.2023
The Explosion Proof range of products has been designed to provide protection against explosions and products to ensure that all major advantages of high-quality fire detection technology can be safely exploited in industrial and hazardous environments. Many difficult sites such as metal, paint, pipelines, chemical, pharmaceutical, oil refineries, and other installations are vulnerable to the risk of explosion. In order to protect the assets and people, they need special solutions for fast and reliable fire detection.
Emergency Lighting System Installation Guide Emergency Lighting System Installation Guide
Jul .20.2023
Emergency lighting system is divided into centralized controlling and non-centralized controlling type, or centralized power supply and non-centralized power supply type. This article talks about emergency lighting system, power supply, emergency light controller installation guide.
Fire Alarm System Device Inspection and Maintenance Fire Alarm System Device Inspection and Maintenance
Jul .05.2023
Installing fire protection facilities and carry out regular maintenance are significant. This article talks about the inspection and maintenance of linear beam smoke detector, aspirating smoke detector, flame detector, manual call point, and strobe sounder.