Gas Fire Suppression System Inspections, Testing and Maintenance

Gas Fire Suppression System Inspection, Testing and Maintenance

Views : 1060
Update time : 2023-05-22 11:30:13

1. Check whether the test device at the end of the sprinkler pipe network on the test floor is normal (whether the water pressure and flow meet the requirements). Check the gas fire suppression panel, and test whether its function is normal.

2. Check whether the pressure of the storage bottle meets the factory filling pressure and design requirements (whether the pointer of the pressure gauge is in the green zone), and whether there is any leakage.

3. Check whether the function of the manual and automatic emergency start, stop device is normal.

4. Clean the solenoid valve regularly, and lubricate them with silicone oil.

5. Simulate the action of the smoke and heat detectors in the fire alarm system. Check whether the ventilation and air conditioning are stopped, whether the fire damper is closed, whether the solenoid valve of the gas cylinder operates within the specified time, whether there is a deflation signal on the control panel, and whether there is a signal in the center, whether the alarm bell and the buzzer are activated.

6. Check if the gas fire suppression system bottles are out of shape or corrupted.

7. Check whether the controlling air pipe is deformed or loose, and check whether the high-pressure hose is deformed, rusted or aged.

8. Check whether the enclosure structure and openings in the gas protection area meet the requirements.
Related News
Read More >>
What is Fire Hose? What is Fire Hose?
Oct .13.2023
A fire hose is a highly pressurized hose that is used to bring water to the fire. It may also transport flame retardants. Fire hoses can be attached to either a fire engine or a fire hydrant, and the pressure is between 800 and 2000 kPa. For reasons of fire safety, it's quite important to have a fire hose inspection as well as all fire protection equipment tested.  If, during a fire emergency, the fire hose fails it could have disastrous results.
Addressable Explosion-proof Fire Alarm System Introduction Addressable Explosion-proof Fire Alarm System Introduction
Aug .08.2023
The Explosion Proof range of products has been designed to provide protection against explosions and products to ensure that all major advantages of high-quality fire detection technology can be safely exploited in industrial and hazardous environments. Many difficult sites such as metal, paint, pipelines, chemical, pharmaceutical, oil refineries, and other installations are vulnerable to the risk of explosion. In order to protect the assets and people, they need special solutions for fast and reliable fire detection.
Emergency Lighting System Installation Guide Emergency Lighting System Installation Guide
Jul .20.2023
Emergency lighting system is divided into centralized controlling and non-centralized controlling type, or centralized power supply and non-centralized power supply type. This article talks about emergency lighting system, power supply, emergency light controller installation guide.
Fire Alarm System Device Inspection and Maintenance Fire Alarm System Device Inspection and Maintenance
Jul .05.2023
Installing fire protection facilities and carry out regular maintenance are significant. This article talks about the inspection and maintenance of linear beam smoke detector, aspirating smoke detector, flame detector, manual call point, and strobe sounder.